Hello, so Im in a new position at a facility that suffers greatly from inefficient operations. I'm trying to compile data to back up justification for my plan of action.

One of my items im addressing is boiler load.

The facility has eight heat exchangers. They are located in mechanical rooms that have significant air flow as the mech room is the intermediary between the return and the AHU. These heat exchangers are uninsulated painted steel. The exchanger shells are 7' long x 6.5" diameter. I came up with the following:

Uninsulated Surface Temp: 122 degrees F Heat Loss: 159.3 BTU/h/ft

Insulated Surface Temp: 75 degrees F Heat Loss: 16.8 BTU/h/ft

Ambient Temperature: 70 degrees F

Air movement @ 1 cu ft min

Heat Exchanger Shell: Painted Steel Shell Dimensions: 7' long x 6.5" Diameter Calculated Shell Surface Area:12.77 sq Ft

Uninsulated BTU lost daily: 48822.26 per heat exchanger

Insulated BTU lost daily: 5136.60 per heat exchanger

Can anyone confirm?

Duplicate Posts
3 posts with the exact same title by 1 other authors
View Details
Author
Account Strength
90%
Account Age
4 years
Verified Email
Yes
Verified Flair
No
Total Karma
92
Link Karma
79
Comment Karma
13
Profile updated: 20 hours ago
Posts updated: 1 year ago

Subreddit

Post Details

We try to extract some basic information from the post title. This is not always successful or accurate, please use your best judgement and compare these values to the post title and body for confirmation.
Posted
3 years ago