Issue with 36kw Tankless Water Heater install (4x 40A 8-2)
Post Body

After install, the kitchen and only the kitchen LED lights flicker very faintly, really only irritating at night. The biggest problem is our induction stove completely changes to a much much sharper and louder pitch when the water heater is running. Sounds like arcing electricity from a low powered stun gun.No other LED lights or appliances are effected. Things to note:

-400A service

-Several LED lights and appliances are actually closer to the tankless than the kitchen is. None are effected.-Several circuits containing LED lights and appliances are closer to the tankless breakers in the electrical panel.

-The induction stoves breaker is actually in a completely separate panel from the tankless.

-Had the power company come out and confirm there wasnt harmonics and/or issues with the transformer or feed to my home. All checked out perfect.

-Individual breakers don't seem to be bad, no out of the oridinary hum from the breaker panel.

-All connections inside the breaker panel have been checked and double checked for tightness.

-Tankless unit itself has been diagnosed and confirmed to be operating inside proper volt and ohm range.

Trying to solve this before it does damage to the stove.

Any help appreciated.

Author
User Disabled
Account Strength
0%
Disabled 1 month ago
Account Age
2 years
Verified Email
Yes
Verified Flair
No
Total Karma
n/a
Link Karma
1
Comment Karma
n/a
Profile updated: 2 days ago
Posts updated: 1 month ago

Subreddit

Post Details

We try to extract some basic information from the post title. This is not always successful or accurate, please use your best judgement and compare these values to the post title and body for confirmation.
Posted
7 months ago